Analog Input Mode Selection
Analog input channels can be divided into voltage and current. For different models, the support of
the voltage and current measurement are not the same.
Mode Available
Number of Analog
Input Channels
Mode Selection:
Voltage
Mode Selection:
Current
ioLogik E2240 8
±150 mV, ±500 mV,
±5 V, ±10 V
0 to 20 mA,
4 to 20 mA
ioLogik E2242 4
±150 mV, 0 to 150 mV,
±500 mV, 0 to 500 mV,
±5 V, 0 to 5 V,
±10 V, 0 to 10 V
0 to 20 mA,
4 to 20 mA
When logged in as an administrator, double click on a channel in the I/O Configuration tab to
configure that channel’s settings. A window will open with configuration options for that channel.
Each AI channel will be configured to measure either voltage or current according to the Range